Specifications
9. CONNECTION TO RKC TEMPERATURE CONTROLLER
9.5 Temperature Controller Side Setting
9 - 47
CONNECTION TO RKC TEMPERATURE CONTROLLER
9
9.5.10 Connecting to AG500
Communication settings
Make the communication settings by operating the key
of the temperature controller.
*1 Adjust the settings with GOT settings.
*2 Select the device address1 without overlapping with that of
other units.
*3 Set the maximum time from the sending of the last character
stop bit from the GOT side until the switching of the GOT
side to the receiving status (until the temperature controller
becomes ready to send). Set as necessary.
*4 When the setting value is set to 0, a communication is not
made.
9.5.11 Connecting to RMC500
Communication settings
Make the communication settings by operating the key
of the temperature controller.
*1 Adjust the settings with GOT settings.
*2 Set the extension time for the data interval time in the
MODBUS communication (which is lower than 24 bit time).
Set when the data time interval exceeds 24 bit time.
*3 Select the device address without overlapping with that of
other units.
*4 When the setting value is set to 0, a communication is not
made.
*5 Set the maximum time from the sending of the last character
stop bit from the GOT side until the switching of the GOT
side to the receiving status (until the temperature controller
becomes ready to send). Set as necessary.
9.5.12 Connecting to MA900, MA901
Communication settings
Make the communication settings by operating the key
of the temperature controller.
*1 Adjust the settings with GOT settings.
*2 Select the device address1 without overlapping with that of
other units.
*3 Set the maximum time from the sending of the last character
stop bit from the GOT side until the switching of the GOT
side to the receiving status (until the temperature controller
becomes ready to send). Set as necessary.
*4 When the setting value is set to 0, a communication is not
made.
9.5.13 Connecting to THV-A1
Communication settings
Make the communication settings by operating the key
of the temperature controller.
*1 Adjust the settings of the GOT side with the temperature
controller settings.
*2 Select the device address1 without overlapping with that of
other units.
*3 Set the maximum time from the sending of the last character
stop bit from the GOT side until the switching of the GOT
side to the receiving status (until the temperature controller
becomes ready to send). Set as necessary.
*4 When the setting value is set to 0, a communication is not
made.
Item Setting range
Communication speed
*1
9600bps, 19200bps, 38400bps
Communication protocol MODBUS
Data bit configuration
*1
(Data bit, Parity bit, Stop
bit)
[8N1]: 8bit, None, 1bit
[8N2]: 8bit, None, 2bit
[8E1]: 8bit, Even, 1bit
[8E2]: 8bit, Even, 2bit
[8O1]: 8bit, Odd, 1bit
[8O2]: 8bit, Odd, 2bit
Device address
*2
(Slave address)
1 to 99
*4
Interval time
*3
0 to 250 (ms)
Item Setting range
Communication speed
*1
9600bps, 19200bps, 38400bps
Communication protocol MODBUS
MODBUS data
*2
Extension time
0 to 255 (ms)
Data bit configuration
*1
(Data bit, Parity bit, Stop
bit)
[8N1]: 8bit, None, 1bit
[8N2]: 8bit, None, 2bit
[8E1]: 8bit, Even, 1bit
[8E2]: 8bit, Even, 2bit
[8O1]: 8bit, Odd, 1bit
[8O2]: 8bit, Odd, 2bit
Device address
*3
(Slave address)
1 to 99
*4
Interval time
*5
0 to 250 (ms)
Item Setting range
Communication speed
*1
9600bps, 19200bps
Data bit configuration
*1
(Data bit, Parity bit, Stop
bit)
[8N1]: 8bit, None, 1bit
[8N2]: 8bit, None, 2bit
[8E1]: 8bit, Even, 1bit
[8E2]: 8bit, Even, 2bit
[8O1]: 8bit, Odd, 1bit
[8O2]: 8bit, Odd, 2bit
Device address
*2
(Slave address)
1 to 99
*4
Interval time
*3
0 to 250 (ms)
Item Setting range
Communication speed
*1
9600bps (fixed)
Data bit configuration
*1
Data bit: 8bit (fixed)
Parity bit: None (fixed)
Stop bit: 1bit (fixed)
Device address
*2
(Slave address)
1 to 99
*4
Interval time
*3
0 to 250 (ms)