9. CONNECTION TO RKC TEMPERATURE CONTROLLER
9.5 Temperature Controller Side Setting
9.5.7 Connecting to RB Series
(1) Communication settings
*1 When the setting value is set to 0, a communication is not
made.
*2 Adjust the settings with GOT settings.
(2) Data bit configuration
(3) Communication setting mode
Set the communication setting mode using the
operation panel of the RB series main unit.
For details of the communication setting mode, refer to
the following.
RB series "Communication Instruction Manual"
9.5.8 Connecting to PF900/900
Communication settings
Make the communication settings by operating the key
of the temperature controller.
*1 Adjust the settings with GOT settings.
*2 Select the device address1 without overlapping with that of
other units.
*3 Set the maximum time from the sending of the last character
stop bit from the GOT side until the switching of the GOT
side to the receiving status (until the temperature controller
becomes ready to send). Set as necessary.
*4 When the setting value is set to 0, a communication is not
made.
9.5.9 Connecting to HA400/401,
HA900/901
Communication settings
Make the communication settings by operating the key
of the temperature controller.
(Communication 1)
(Communication 2)
*1 Adjust the settings with GOT settings.
*2 Select the device address1/2 without overlapping with that of
other units.
*3 Set the maximum time from the sending of the last character
stop bit from the GOT side until the switching of the GOT
side to the receiving status (until the temperature controller
becomes ready to send). Set as necessary.
*4 When the setting value is set to 0, a communication is not
made.
Item Setting range
Communication protocol 1: MODBUS
Device address
(Slave address)
*1
1 to 99
Communication speed
*2
2: 9600bps
3: 19200bps
Data bit configuration (2) Refer to the data bit configuration.
Interval time 0 to 250
Set value Data bit Parity bit Stop bit
0 8 None 1
1 8 None 2
28Even1
38Even2
48Odd1
58Odd2
Item Setting range
Communication speed 1
*1
9600bps, 19200bps, 38400bps,
57600bps
Communication protocol 1 MODBUS
Data bit configuration 1
*1
(Data bit, Parity bit, Stop
bit)
[8N1]: 8bit, None, 1bit
[8N2]: 8bit, None, 2bit
[8E1]: 8bit, Even, 1bit
[8E2]: 8bit, Even, 2bit
[8O1]: 8bit, Odd, 1bit
[8O2]: 8bit, Odd, 2bit
Device address 1
*2
(Slave address 1)
1 to 99
*4
Interval time
*3
0 to 250 (ms)
Item Setting range
Communication speed 1
*1
9600bps, 19200bps, 38400bps
Data bit configuration 1
*1
(Data bit, Parity bit, Stop
bit)
[8N1]: 8bit, None, 1bit
[8N2]: 8bit, None, 2bit
[8E1]: 8bit, Even, 1bit
[8E2]: 8bit, Even, 2bit
[8O1]: 8bit, Odd, 1bit
[8O2]: 8bit, Odd, 2bit
Device address 1
*2
(Slave address 1)
1 to 99
*4
Interval time
*3
0 to 250 (ms)
Item Setting range
Communication speed 2
*1
9600bps, 19200bps, 38400bps
Data bit configuration 2
*1
(Data bit, Parity bit, Stop
bit)
[8N1]: 8bit, None, 1bit
[8N2]: 8bit, None, 2bit
[8E1]: 8bit, Even, 1bit
[8E2]: 8bit, Even, 2bit
[8O1]: 8bit, Odd, 1bit
[8O2]: 8bit, Odd, 2bit
Device address 2
*2
(Slave address 2)
1 to 99
*4
Interval time
*3