Specifications
9. CONNECTION TO RKC TEMPERATURE CONTROLLER
9.5 Temperature Controller Side Setting
9 - 43
CONNECTION TO RKC TEMPERATURE CONTROLLER
9
Unit address settings
Set the unit address using the unit address setting
switch.
9.5.3 Connecting to Z-TIO, Z-DIO,
Z-CT
(1) Communication settings
Make the communication settings of the temperature
controller.
*1 Adjust the settings with GOT settings.
*2 Select the module address without overlapping with that of
other units.
(2) Setting DIP switches
Make the settings of transmission speed, data bit
configuration, communication protocol
Unit address setting switch
Setting range: 0 to F
Item Setting range
Communication speed
*1
9600bps, 19200bps, 38400bps
Communication protocol MODBUS
Data bit configuration
Data bit : 8bits, Parity : None
Data bit : 8bits, Parity : Even
Data bit : 8bits, Parity : Odd
Stop bit : 1bit (fixed)
Unit address
*2
0 to F
Interval time 0 to 250ms
Setting item Set value
Switch position
1 2 3 4 5 6
Communication
speed
9600bps ON OFF
19200bps OFF ON
38400bps ON ON
Data bit
configuration
Data bit: 8bits,
Parity: None
OFF OFF ON
Data bit: 8bits,
Parity: Even
OFF ON ON
Data bit: 8bits,
Parity: Odd
ON ON ON
Communication
protocol
MODBUS ON
12345678
ON
OFF ON
Front side Right side
Dip switch