Specifications
9. CONNECTION TO RKC TEMPERATURE CONTROLLER
9.4 GOT Side Settings
9 - 39
CONNECTION TO RKC TEMPERATURE CONTROLLER
9
9.4 GOT Side Settings
9.4.1 Setting communication
interface (Communication
settings)
Set the channel of the connected equipment.
1. Select [Common] [Controller Setting] from the
menu.
2. The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3. Set the following items.
• Manufacturer: RKC
• Controller Type: RKC SR Mini HG
• I/F: Interface to be used
• Driver: RKC SR Mini HG(MODBUS)
4. The detailed setting is displayed after Manufacturer,
Controller Type,
I/F, and Driver are set.
Make the settings according to the usage
environment.
9.4.2Communication detail settings
Click the [OK] button when settings are completed.
POINTPOINTPOINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
9.4.2 Communication detail settings
2.
3.
4.
Click!
Item Description Range
Transmissio
n Speed
Set this item when change the transmission
speed used for communication with the
connected equipment.
(Default: 9600bps)
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
Data Bit
Set this item when change the data length used
for communication with the connected
equipment.
(Default: 8bits)
7bits/8bits
Stop Bit
Set this item when change the data length used
for communication with the connected
equipment.
(Default: 1bit)
1bit/2bits
Parity
Specify whether or not to perform a parity
check, and how it is performed during
communication.
(Default: No)
None
Even
Odd
Retry
Set the number of retries to be performed when
a communication error occurs.
(Default: 0time)
0 to 5times
Timeout
Time
Set the time period for a communication to time
out.
(Default: 3sec)
3 to 30sec
Delay Time
Set this item to adjust the transmission timing
of the communication request from the GOT.
(Default: 0ms)
0 to 300ms
Format
Select the communication format.
(Default: 1)
Format 1:
Accessible to H-PCP-J, H-PCP-A, H-PCP-B,
SRZ, FB, PF, HA, MA, RMC, SRX, B400 series
Format 2:
Accessible to CB series, RB, AG, THV, SA, SB1
series
1/2