Specifications
8 - 30
8. CONNECTION TO YOKOGAWA TEMPERATURE CONTROLLER
8.5 Temperature Controller Side Setting
8.5.2 Connecting to UT100 Series
Communication settings
Make the communication settings by operating the key
of the temperature controller.
*1 Adjust the settings with GOT settings.
*2 Avoid duplication of the address with any of the other units.
8.5.3 Connecting to UT2000 Series
Communication settings
Make the communication settings using setting
switches.
*1 Adjust the settings with GOT settings.
*2 Avoid duplication of the station No. with any of the other
units.
Settings by switch
(1) Settings of the transmission speed and the parity
Make those settings by operating the communication
setting Rotary switch.
(2) Communication mode settings
Make this setting by operating the communication
mode select DIP SW.
(3) A setting of the station No.
Make this setting by operating the station No. select
Rotary switch.
8.5.4 Connecting to UTAdvanced
Series
Communication settings
Make the communication settings by operating the key
of the temperature controller.
*1 Adjust the settings with GOT settings.
*2 Avoid duplication of the address with any of the other units.
Item Set value
Transmission speed 9600bps
Data bit
*1
7bits, 8bits
Parity bit
*1
Even, odd, none
Stop bit
*1
1bit, 2bits
Address
*1*2
1 to 99
Protocol selection
*1
0: PC link communication (without sum check)
1: PC link communication (with sum check)
Item Set value
Transmission speed 9600bps
Data bit
*1
8bits (fixed)
Parity bit
*1
Even, odd, none
Stop bit
*1
1bit (fixed)
Station No.
*1*2
1 to 16
Communication mode PC link communication mode
Switch position
Transmission
speed
Parity bit
0
9600bps
None
1Odd
2 Even
Communication mode
select DIP SW
Communication setting
Rotary switch
Station No. select
Rotary switch
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
Switch position Communication mode
ON PC link communication mode
Switch position Station No.
01
12
23
34
45
56
67
78
89
910
A11
B12
C13
D14
E15
F16
Item Set value
Transmission speed
*1
9600bps, 19200bps, 38400bps
Data bit
*1
7bits, 8bits
Parity bit
*1
Even, odd, none
Stop bit
*1
1bit, 2bits
Address
*1*2
1 to 99
Minimum response time
*1
0 to 10 (x 10ms)
Protocol selection
*1
0: PC link communication (without sum check)
1: PC link communication (with sum check)
ON
OFF
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9