Specifications

7. CONNECTION TO YOKOGAWA PLC
7.3 Ethernet Connection
7 - 17
7
CONNECTION TO YOKOGAWA PLC
7.3.2 GOT Side Settings
Setting communication interface
(Communication settings)
Set the channel of the connected equipment.
1. Select [Common] [Controller Setting] from the
menu.
2. The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3. Set the following items.
Manufacturer: YOKOGAWA
Controller Type: STARDOM/FA500/FA-M3
I/F: Interface to be used
Driver: Ethernet (YOKOGAWA), Gateway
4. The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
7.3.2 Communication detail settings
Click the [OK] button when settings are completed.
POINTPOINTPOINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
Communication detail settings
Make the settings according to the usage environment.
*1 Each of [GOT Station] set in the communication detail setting
and [Station] set in the Ethernet setting must be set to
different station numbers.
Ethernet setting
POINTPOINTPOINT
(1) Communication interface setting by the Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
GOT2000 Series User's Manual (Utility)
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
2.
3.
4.
Click!
Item Description Range
GOT Net No.
Set the network No. of the GOT.
(Default: 1)
1 to 239
GOT Station
*1
Set the station No. of the GOT.
(Default: 1)
1 to 64
GOT Ethernet
Setting
Set the GOT IP address, subnet
mask, default gateway, peripheral S/
W communication port No.,
transparent port No.
GOT
Ethernet setting
GOT
Communication
Port No.
Set the GOT port No. for the
connection with the Ethernet
module.
(Default: 5017)
1024 to 5010,
5014 to 65534
(Except for 5011,
5012, 5013 and
49153)
Retry
Set the number of retries to be
performed when a communication
timeout occurs.
When receiving no response after
retries, the communication times
out.
(Default: 3times)
0 to 5times
Startup Time
Specify the time period from the
GOT startup until GOT starts the
communication with the PLC CPU.
(Default: 3sec)
3 to 255sec
Timeout Time
Set the time period for a
communication to time out.
(Default: 3sec)
1 to 90sec
Delay Time
Set the delay time for reducing the
load of the network/destination PLC.
(Default: 0ms)
0 to 10000
( 10 ms)