Specifications
7. CONNECTION TO YOKOGAWA PLC
7.2 Serial Connection
7 - 13
7
CONNECTION TO YOKOGAWA PLC
(2) Data format setting switch
Set the data length, parity, stop bit and checksum
consistent with the corresponding settings on the GOT
side.
For the settings on the GOT side, refer to the following.
7.2.5 ■ Communication detail settings
(3) Station No. switch (LC02-0N only)
7.2.11 Connecting to STARDOM
Make the communication settings as shown below.For
details of the communication settings, refer to the following
manual.
Peripheral Software Manual for YOKOGAWA
PLC
POINTPOINTPOINT
Connection between STARDOM and the PC for
communication settings
For the communication settings of STARDOM,
STARDOM and the PC for communication settings
must be connected to Ethernet using the Resource
Configurator (peripheral software).
COM port setting
Make the settings on the FCX Maintenance Page for
STARDOM.
1. Select [Reboot (Maintenance Mode)] on the Reboot
screen of the FCX Maintenance Page to set the
maintenance mode.
2. Set the COM1 port driver to be used.Execute [JEROS
Basic Setting File] from the [Edit System Setting File]
screen on the FCX Maintenance Page.
Confirm that the line of [Com1SioDriver] is as follows.
Com1SioDriver=DUONUS_SIO
3. Set the COM1 port to be used.Execute [COM1 Port
Setting File] from the [Edit System Setting Files]
screen on the FCX Maintenance Page.Make the
settings as follows according to the communication
specifications on the setting screen.
Leave the settings as default if not listed on the
communication setting items.
(Communication setting items) ( ) in the table shows
the names on the FCX Maintenance Page.
*1 Adjust the settings with GOT communication settings.
7.2.5 ■ Communication detail settings
Switch No. Description Settings
1 Data bit
ON (8bits),
OFF (7bits)
2
Parity
ON (done),
OFF (none)
3
ON (even),
OFF (odd)
4 Stop bit
ON (2bits),
OFF (1bit)
5 Checksum
ON (done),
OFF (none)
6
End character
specification
OFF (none)
7 Protect function OFF (disabled)
8—OFF
Rotary
switch
Description
Settings
For RS-
232
communi
cation
For RS-
422
communi
cation
1)
Station No.
(10's digit)
00
2)
Station No.
(1's digit)
12
1
2
3
4
5
6
7
8
OFFON
0
6
5
4
7
3
8
2
9
1
0
6
5
4
7
3
8
2
9
1
STATION NO.
Item Set value
Transmission speed (Baudrate)
*1
4800bps, 9600bps,
19200bps, 38400bps,
57600bps, 115200bps
Data length (DataBitLength)
*1
8bits, 7bits
Stop bit (StopBitLength)
*1
1bit, 2bits
Parity bit (Parity)
*1
none/odd/even
Baudrate = *1
DataBitLength = *1
StopBitLength = *1
Parity = *1
FifoMode = YES
InitialDTRState = ON
SendFlowControlMode = CTS
ReceiveFlowControlMode = DTR