Specifications
7. CONNECTION TO YOKOGAWA PLC
7.2 Serial Connection
7 - 3
7
CONNECTION TO YOKOGAWA PLC
7.2 Serial Connection
7.2.1 System configuration for connecting to FA-M3/M3V
When using the conversion cable
*1 Product manufactured by YOKOGAWA Electric Corporation. For details of the product, contact Yokogawa Electric Corporation.
*2 CPU port/D-Sub 9-pin conversion cable
*3 SIO port adapter cable
*4 Including the length of the CPU port/D-Sub 9-pin conversion cable or the SIO port adapter cable.
Conversion
cable
FA-M3/M3V
GOT
Connection cable
Communication driver
YOKOGAWA
FA500/FA-M3/STARDOM
PLC Connection cable GOT
Number of
connectable
equipment
Model
name
Conversion
cable
*1
Commun
ication
Type
Cable model
Connection diagram number
Max.
distance
Option device Model
F3SP05
F3SP08
F3SP21
F3SP22-0S
F3SP25
F3SP28
F3SP35
F3SP38
F3SP53
F3SP58
F3SP59
KM10-0C
*2
RS-232
GT09-C30R20301-9P(3m)
or
RS-232 connection diagram 1)
15m
*4
- (Built into GOT)
1 GOT for 1 PLC
GT15-RS2-9P
F3SP66
F3SP67
KM10-0S
*3
RS-232
GT09-C30R20301-9P(3m)
or
RS-232 connection diagram 1)
15m
*4
- (Built into GOT)
GT15-RS2-9P