Specifications

6 - 28
6. CONNECTION TO YASKAWA PLC
6.3 Ethernet Connection
6.3.5 PLC side setting (CP-9200SH
series, CP-312, CP-317
series)
POINTPOINTPOINT
YASKAWA PLC
For details of YASKAWA PLCs, refer to the following
manuals.
YASKAWA PLC user's Manual
Parameter settings
Make the parameter settings with a peripheral tool.
(1) Settings for CP-218IF
*1 Be sure to set the values above for the address so that the
GOT communicates with the programmable controller
correctly.
For the Host Address setting on the GOT side, refer to the
following.
6.3.2 Ethernet setting
(2) Settings for CP-218IF
Settings by DIP switch
(1) Settings for 218TXB
Set the DIP switch (SW2) as follows.
*1 Turn off all the unused switches.
When even one of those switches is on, the PLC may not
normally operate.
*2 When the PLC is started with the TEST switch on, the
module starts the self-diagnosis and may not perform the
communication.
Turn off the switch before the communication is started.
Item Set value
Module Type CP-218
CPU Number 01
Circuit Number 01
Hot Swapping
Item CNO 03 CNO 04 CNO 05
Local Port 10500 10501 10030
Node IP
Address
*1
192.168.001.018 192.168.001.020 192.168.001.073
Node
Port
*1
05016 05017 21001
Connection
Type
TCP TCP UDP
Protocol
Type
Extended
MEMOBUS
Extended
MEMOBUS
Extended
MEMOBUS
Code BIN BIN BIN
Item Set value
Transmission
parameter
setting
IP Address IP address for 218TXB
Response Time Not required
Count of Retry
(Number of Retries)
Not required
Connection
parameter
setting
Connection Number 1
Local Port 10500
Node IP Address Local IP address of GOT
Node Port Local port No. of GOT
Connection Type UDP
Protocol Type Extended MEMOBUS
Code BIN
Node Name Any string
Setting Item Set value Setting range
N/O Mode Selection ON
ON: Extended mode (13
channels, up to 1024 words)
OFF: Basic mode (10 channels,
up to 512 words)
-
*1
Not used OFF -
10/100
Transmission
Speed
OFF
ON :10Mbps
OFF :100Mbps
F/H
Transmission
Mode
OFF
ON: Full duplex mode
OFF: Half duplex mode
INIT Initial Startup OFF
ON: Start up by the default IP
address and the engineering port
No.
OFF: Start up by the IP address
and the engineering port No. set
for CP-717
TEST
*2
Test OFF
ON: The module starts the self-
diagnosis when the PLC is
started.
OFF: The module does not start
the self-diagnosis when the PLC
is started.
N/O
10/100
F/H
TEST
INIT
OFF
ON
-
-
-