Specifications
6 - 22
6. CONNECTION TO YASKAWA PLC
6.3 Ethernet Connection
6.3.3 GOT Ethernet setting
Ethernet setting
*1 Connection with the PLC is unavailable if the IP address is
the default value. Set the value to the IP address of the PLC
to be connected.
*2 Each of [GOT Station] set in the communication detail setting
and [Station] set in the Ethernet setting must be set to
different station numbers.
■ Communication detail settings
Item Description Range
GOT
IP Address
Set the IP address of the GOT.
(Default: 192.168.0.18)
0.0.0.0 to
255.255.255.255
Subnet
Mask
Set the subnet mask for the sub
network.(Only for connection via
router)
If the sub network is not used, the
default value is set.
(Default: 255.255.255.0)
0.0.0.0 to
255.255.255.255
Default
Gateway
Set the router address of the
default gateway where the GOT is
connected.(Only for connection via
router)
(Default: 0.0.0.0)
0.0.0.0 to
255.255.255.255
Peripheral S/W
Communication
Port No.
Set the GOT port No. for the S/W
communication. (Default: 5015)
1024 to 5010
5014 to 65534
(Except for 5011,
5012, 5013 and
49153)
Transparent Port
No.
Set the GOT port No. for the
transparent function.
(Default: 5014)
1024 to 5010
5014 to 65534
(Except for 5011,
5012, 5013 and
49153)
Item Description Set value
Host
The host is displayed. (The host is
indicated with an asterisk (*).)
―
Net No.
Set the network No. of the
connected Ethernet module.
(Default: blank)
1 to 239
Station
*2
Set the station No. of the
connected Ethernet module.
(Default: blank)
1 to 64
Type YASKAWA (fixed) YASKAWA (fixed)
IP address
*1
Set the IP address of the
connected Ethernet module.
(Default: blank)
PLC side IP
address
Port No.
Set the port No. of the connected
Ethernet module.
(Default: 10500)
256 to 65534
Communication
format
Select a communication protocol.
(Default: UDP)
UDP, TCP