5. CONNECTION TO FUJI TEMPERATURE CONTROLLER
5.6 Device Range that Can Be Set
5 - 19
5
CONNECTION TO FUJI TEMPERATURE CONTROLLER
5.6 Device Range that Can Be Set
The device ranges of controller that can be used for GOT are as follows.
Note that the device ranges in the following tables are the maximum values that can be set in GT Designer3.
The device specifications of controllers may differ depending on the models, even though belonging to the same series.
Please make the setting according to the specifications of the controller actually used.
When a non-existent device or a device number outside the range is set, other objects with correct device settings may
not be monitored.
Setting item
*1 The following shows the relation between station numbers of the temperature controller and the GOT data register.
POINTPOINTPOINT
The device setting of FUJI temperature controller
Devices are set with the coil and register numbers of the temperature controller.
For parameters (such as an address map of coil/register number and a parameter) corresponding to each number,
refer to the manual of the temperature controller to be used.
Item Description
Device
*1
Set the device name, device number, and bit number.
The bit number can be set only when specifying the bit of word device.
Information Displays the device type which is selected in [Device].(Bit/Word)
Network
Set the monitor target of the set device.
Station No.
To monitor the temperature controller of the specified station No.
1 to 119, 216 to 255 : To monitor the temperature controller of the specified station No.
200 to 215: To specify the station No. of the temperature controller to be monitored by the value of
GOT data register (GD).
*1
Station No. GOT data register (GD) Setting range
200 GD10
1 to 255
(If setting a value outside the
range above, a device range
error occurs.)
201 GD11
::
214 GD24
215 GD25