Specifications

5. CONNECTION TO FUJI TEMPERATURE CONTROLLER
5.5 Temperature Controller Side Setting
5 - 15
5
CONNECTION TO FUJI TEMPERATURE CONTROLLER
5.5.3 Connecting to PXH9
Communication settings
Make the communication settings by operating the key
of the temperature controller.
(1) RS-485 communication settings
*1 Adjust the settings with GOT settings.
*2 Avoid duplication of the station No. with any of the other
units.
(2) RS-232 communication settings (PC loader
communication)
*1 Adjust the settings with GOT settings.
5.5.4 Connecting to interface
converter (RC-77)
Communication settings
Make the communication settings using setting
switches.
*1 Adjust with GOT and temperature controller settings.
Settings by switch
(1) Settings of transmission speed and MANUAL-AUTO
Item Set value
Transmission speed
*1
9600bps, 19200bps, 38400bps
Data bit 8bits (fixed)
Parity bit
*1
Even, Odd, None
Stop bit 1bit (fixed)
Station No.
*2
1 to 255
Item Set value
Transmission speed
*1
9600bps, 19200bps, 38400bps
Data bit 8bits (fixed)
Parity bit
*1
Even, Odd, None
Stop bit 1bit (fixed)
Station No. 1 (fixed)
Item Set value
Transmission speed
*1
9600bps, 19200bps, 38400bps
MANUAL-AUTO AUTO
DCE/DTE switching DCE
RS-422/485 switching RS-485
Terminating resistor
selection
OFF
Setting item Set value
Switch No.
1 2 3 4
Transmission
speed
9600bps ON ON OFF
19200bps OFF OFF ON
38400bps ON OFF ON
MANUAL-
AUTO
AUTO ON
Terminating resistor
selection switch
RS-422/485 switch
RS-485 communication
setting switch
DCE/DTE switch
DCE-DTE
RTS-DTR
RESET
BIT RATE
MANUAL-AUTO
MONITOR
1
2
3 4
5
6
422-485
TERMINATOR
ON-OFF
POWER
DATA OUT
TXD+
TXD-
FG
RXD+
RXD-
DATA CH
FG
BIT RATE
MANUAL-AUTO MONITOR
123456