Specifications

5 - 14
5. CONNECTION TO FUJI TEMPERATURE CONTROLLER
5.5 Temperature Controller Side Setting
5.5 Temperature Controller Side Setting
POINTPOINTPOINT
(1) FUJI temperature controller
For details of FUJI temperature controller, refer to
the following manual.
User's Manual of the FUJI temperature
controller
(2) Interface converter
For details on communication settings of the
interface converter, refer to the following manual.
User's Manual of interface converter
5.5.1 Connecting to PXR3/4/5/9
Communication settings
Make the communication settings by operating the key
of the temperature controller.
*1 Adjust the settings with GOT settings.
*2 Avoid duplication of the station No. with any of the other
units.
5.5.2 Connecting to PXG4, PXG5 or
PXG9
Communication settings
Make the communication settings by operating the key
of the temperature controller.
(1) RS-485 communication settings
*1 Adjust the settings with GOT settings.
*2 Avoid duplication of the station No. with any of the other
units.
*3 Set as necessary.
(2) RS-232 communication settings (PC loader
communication)
Model name Refer to
Temperature controller
PXR3, PXR4, PXR5,
PXR9
5.5.1
PXG4, PXG5, PXG9 5.5.2
PXH9 5.5.3
Interface converter
RC-77 5.5.4
SI-30A 5.5.5
KS-485 5.5.6
K3SC-10 5.5.7
Item Set value
Transmission speed 9600bps (fixed)
Data bit 8bits (fixed)
Parity bit
*1
Even, Odd, None
Stop bit 1bit (fixed)
Station No.
*2
1 to 255
Communication protocol MODBUS
Item Set value
Transmission speed
*1
9600bps, 19200bps
Data bit 8bits (fixed)
Parity bit
*1
Even, Odd, None
Stop bit
*1
1bit (fixed)
Station No.
*2
1 to 255
Communication
permissions
*3
Read only permission or read and overwrite
permission
Item Set value
Transmission speed 9600bps (fixed)
Data bit 8bits (fixed)
Parity bit None (fixed)
Stop bit 1bit (fixed)