Specifications

4 - 18
4. CONNECTION TO FUJI PLC
4.2 Serial connection
(b) Setting of Transmission speed, Stop bit, Data bit,
Parity bit, Initializing method
Connecting to NC1L-RS4
(1) Communication settings
Make the communication settings using setting
switches.
*1 Adjust the settings with GOT settings.
*2 Avoid duplication of the station No. with any of the other
units.
*3 Turn ON the terminating switch of a general-purpose
interface module which will be a terminal.
(2) Settings by switch
Make the communication settings using each setting
switch.
(a) Setting of the MODE
Make the MODE settings using the MODE switch.
Setting item Set value
Switch No.
1 2 3 4 5 6 7 8
Transmission
speed
9600bps ON
OFF
ON
19200bps
OFF
ON ON
Stop bit
1bit ON
2bits
OFF
Data bit
7bits ON
8bits
OFF
Parity bit
Even ON
Odd
OFF
Done ON
None
OFF
Initializing
method
By switch ON
For the NV1L-RS2 For the NC1L-RS2
Item Set value
MODE
Command-setting-type start-stop
synchronization, nonsequence format
Transmission speed
*1
9600bps, 19200bps
Data bit
*1
8bits or 7bits
Parity bit
*1
Even or Odd
Done, None
Stop bit
*1
1bit, 2bits
Initializing method By switch
Station No.
*1*2
0 to 99
Terminating resistor
*3
ON or OFF
MODE Switch position
Command-setting-type start-stop
synchronization, nonsequence
format
3
MODE switch
RS-485 station No.
switches
Terminator switch
Character configuration
switches
(Front view) (Rear view)