Specifications
4 - 16
4. CONNECTION TO FUJI PLC
4.2 Serial connection
(For FUJI MICREX-SX SPH)
*1 Leave the setting as default. If the set value is changed,
communication with the PLC is disabled.
POINTPOINTPOINT
(1) Host address
When connecting to PLC by RS-232
communication, set the Host Address to "0".
(2) Communication interface setting by the Utility
The communication interface setting can be
changed on the Utility's [Communication Settings]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
GOT2000 Series User's Manual (Utility)
(3) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
Item Description Range
Transmission
Speed
*1
Set this item when change the
transmission speed used for
communication with the connected
equipment. (Default: 38400bps)
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
Data Bit
*1
Set this item when change the data
length used for communication with
the connected equipment.
(Default: 8bits)
7bits/8bits
Stop Bit
*1
Specify the stop bit length for
communications. (Default: 1bit)
1bit/2bits
Parity
*1
Specify whether or not to perform a
parity check, and how it is performed
during communication.
(Default: Even)
None
Even
Odd
Retry
Set the number of retries to be
performed when a communication
error occurs. (Default: 3time)
0 to 5times
Timeout Time
Set the time period for a
communication to time out.
(Default: 3sec)
1 to 30sec
Delay Time
Set this item to adjust the
transmission timing of the
communication request from the
GOT. (Default: 0ms)
0 to 300ms