Instruction manual
7. EXAMPLES OF SEQUENCE PROGRAMS
IMSRM52-E5
62
7.4 Example of Set Data Change Sequence Program
If M27 (Set data transfer) is turned on, the set data is written in the H-LNK-A module.
When the control STOP state is changed to the control RUN state, set the setting flag
after a delay time of about 5 seconds by using a timer for initialize processing in the
temperature control unit.
Temperature set value (SV)
(CH1 = 150)
Temperature set value (SV)
(CH2 = 100)
Data transfer
Setting extension No. setting
(Extension No. = 3)
Set value setting
Setting flag setting
(T1: Write delay timer)
PLS M28
SM1036
M64: Extended setting completion
M24: Extended setting flag
M27: Set data transfe
r
M64 M24 M27
SET M24
M28
PLS M29
M64
RST M24
M29
RST M27
MOV K150 D57
MOV K100 D58
SET M17
SET M18
TO H0 H1E0 D57 K16
(RWw)
(Extended setting completion)
T1
M26