Instruction manual

6. REMOTE INPUT/OUTPUT AND REMOTE REGISTERS
IMSRM52-E5
49
Continued from the previous page.
Exten-
sion
No.
Name
Attri-
bute
Data range Description
Factory set
value
45
Cannot be used.
46
Cannot be used.
47
Cannot be used.
48
Control loop break alarm
(LBA) status
RO 0: Alarm off
1: Alarm on
Displays the output status of
the control loop break alarm
(LBA).
49
Loop break alarm (LBA)
use selection
R/W 0: Unused
1: Used
Sets use/unuse of the control
loop break alarm (LBA).
0
50
LBA time setting R/W 1 to 7200 seconds Sets the loop break alarm
(LBA) time.
480
51
LBA Deadband R/W Input span Sets the region in which no
loop break alarm (LBA) is
issued
0
52
Cannot be used.
53
Cannot be used.
54
Cannot be used.
55
Cannot be used.
56
Cannot be used.
57
Cannot be used.
58
Cannot be used.
59
Cannot be used.
60
Cannot be used.
61
Cannot be used.
62
Cannot be used.
63
Cannot be used.
z Heater break alarm function
The current transformer (CT) input measured value [Extension No.2] and heater break alarm set value
[Extension No.24] are used by the heater break alarm function. The heater break alarm set value is set
to about 85 % of the current transformer (CT) input measured value. However, for a heater having a
slightly delayed current rise characteristic, change the set value by lowering the set value if necessary.
Heater break alarm function:
The presence or absence of heater break is determined by comparing the current flowing through the
heater (current transformer input measured value: Extension No. 2) to the current preset and assumed
to be abnormal (heater break alarm set value: Extension No. 24). The presence or absence of heater
break can be recognized by the ON/OFF condition of the heater break alarm (remote input).
Continued on the next page.