Instruction manual

6. REMOTE INPUT/OUTPUT AND REMOTE REGISTERS
IMSRM52-E5
48
Continued from the previous page.
Exten-
sion
No.
Name
Attri-bu
te
Data range Description
Factory set
value
30
Operation mode
setting
R/W 0: Unused
1: Only monitoring
2: Only monitoring
and alarm
3: Normal
Selects the temperature
control channel operation
mode.
3
31
Set value monitoring RO Within input range Displays the set value now
used for control. If the
function of limiting the
rate of setting change is
used, indicates the set
value now changing.
32
Error code RO For details of the data,
Refer to page 50.
Displays the error code
during system error
occurrence at operation or
power on. Only [RWrn] data
is effective.
33
Memory area number R/W 1 to 8 Changes the control area.
Monitor: Only [RWrn]
data is effective.
Setting: Only [RWwm]
data is ffective.
1
34
Control response
designation parameters
R/W 0: Slow
1: Medium
2: Fast
Sets the control response
designation parameter in PID
control.
0 *
35
Cannot be used.
36
Cannot be used.
37
Cannot be used.
38
Cannot be used.
39
Cannot be used.
40
Cannot be used.
41
Cannot be used.
42
Cannot be used.
43
Cannot be used.
44
Cannot be used.
* Heat control: 0 (Slow)
Heat/cool control: 2 (Fast)
Continued on the next page.