Instruction manual
6. REMOTE INPUT/OUTPUT AND REMOTE REGISTERS
IMSRM52-E5
46
Continued from the previous page.
Exten-
sion
No.
Name
Attri-
bute
Data range Description
Factory set
value
7
Derivative time (D) R/W
0 to 3600 seconds
(0: PI control)
Sets the derivative time which
predicts output changes in
proportional control to prevent
ripples and thus improve
control stability.
60
8
PV bias R/W −5.00 to +5.00 % of span
Sets the bias added to the
measured value to perform
sensor correction.
0.00
9
First alarm set value R/W Within input range or
within span range
Sets the first alarm set value.
Differs
depending
on the
specification.
10
Second alarm
set value
R/W Within input range or
within span range
Sets the second alarm set
value.
11
Cannot be used.
− − − −
12
Cannot be used.
− − − −
13
Cannot be used.
− − − −
14
Cannot be used.
− − − −
15
Cannot be used.
− − − −
16
Cannot be used.
− − − −
17
Control RUN/STOP
status
RO 0: Control stop
1: Control run
Displays the control run or
stop status. Only [RWrn] data
is effective. Control is started
or stopped by remote output
[RYnF].
−
18
Proportioning cycle time
(Heat-side)
R/W 1 to 100 seconds
Sets the proportioning
cycle time (heat-side) in P, PI
or PID control (including
heat/cool PID control).
Setting will be invalid with
output of current/voltage.
20
a
19
Auto/Manual transfer R/W 0: Auto
1: Manual
Performs Auto (normal
automatic control
operation)/Manual (manual
control operation) transfer.
0
a
Relay contact output: 20 seconds
Voltage pulse output, open collector output, triac output: 2 seconds
For current/voltage output: Setting is ineffective.
Continued on the next page.