6. REMOTE INPUT/OUTPUT AND REMOTE REGISTERS
IMSRM52-E5
45
6.4 Extension No.
The Extension No. is that specified by the remote output [RYn0 to RYn5 or RYn6 to RYnB] to select
data processed by the remote register.
If the necessary data is selected from the following table and its Extension No. is specified by the
remote output [RYn0 to RYn5 or RYn6 to RYnB], it can be processed by the remote register.
List of Extension Nos.
Attribute
RO: Read only
Direction: Remote device station (Temperature control unit)
→
Master station (PLC)
WO: Write only
Direction: Remote device station (Temperature control unit)
←
Master station (PLC)
R/W: Common to read and write
Direction: Remote device station (Temperature control unit)
↔
Master station (PLC)
Exten-
sion
No.
Name
Attri-
bute
Data range Description
Factory set
value
0
Temperature
measured value (PV)
RO Within input range Displays the temperature
measured value.
−
1
Manipulated output
(Heat-side)
RO −5.0 to +105.0 % Displays the manipulated
output on the heat-side.
−
2
CT input measured
value *
RO 0.0 to 30.0 A:
CTL-6 type
0.0 to 100.0 A:
CTL-12 type
Displays the current
measured value detected
by the CT sensor of the
H-CT-A module.
−
3
Temperature
set value (SV)
R/W Within input range
(Within setting
limiter range)
Sets the target value in
temperature control.
0
4
PID/AT transfer R/W 0: PID control
1: Autotuning (AT)
Selects PID control or
autotuning (AT).
If “1” is selected, AT
immediately starts.
In addition, suspends AT
immediately when “0” is set
during autotuning (AT)
execution.
0
5
Proportional band
(Heat-side)
R/W 0.1 to 1000.0 % of span Sets the proportional band
(heat-side) in P, PI or
PID control (including
heat/cool PID control).
3.0
6
Integral time (I) R/W 1 to 3600 seconds Sets the integral time to
eliminate offset occurring in
proportional control.
240
* For details of the heater break alarm function, refer to page 49.
Continued on the next page.