Instruction manual

6. REMOTE INPUT/OUTPUT AND REMOTE REGISTERS
IMSRM52-E5
38
List of remote output (4 stations occupied, Temperature control 16 channels)
Direction: Master station (PLC) Remote device station (Temperature control unit)
Address Details
RYn0
b0
RYn1
b1 Extension No. setting for display *
RYn2
b2 Specify any one of 0 to 63 by RYn0 to RYn5 (b0 to b5) ON/OFF.
RYn3
b3 For details of 0 to 63, refer to 6.4 Extension No. (P. 45).
RYn4
b4
RYn5
b5
RYn6
b0
RYn7
b1 Extension No. setting for setting *
RYn8
b2 Specify any one of 0 to 63 by RYn6 to RYnB (b0 to b5) ON/OFF.
RYn9
b3 For details of 0 to 63, refer to 6.4 Extension No. (P. 45).
RYnA
b4
RYnB
b5
RYnC
Extended display flag
1
RYnD
Extended setting flag
1
RYnE
Unused
RYnF
Control RUN/STOP transfer (OFF: Control stop, ON: Control run)
* RYn0 to RYn5 (b0 to b5) and RYn6 to RYnB (b0 to b5) bit patterns become as follows.
Extension No. for display
RYn5 RYn4 RYn3 RYn2 RYn1 RYn0
b5 b4 b3 b2 b1 b0
Extension No. for setting
RYnB RYnA RYn9 RYn8 RYn7 RYn6
b5 b4 b3 b2 b1 b0
Example: Extension No. for setting is set to “49.”
b5 b4 b3 b2 b1 b0
1 1 0 0 0 1
Ð
RYnB RYnA RYn9 RYn8 RYn7 RYn6
ON ON OFF OFF OFF ON
1
For details, refer to 6.5 Flag Operation (P. 51).
Continued on the next page.