Instruction manual

6. REMOTE INPUT/OUTPUT AND REMOTE REGISTERS
IMSRM52-E5
35
Continued from the previous page.
Direction: Remote device station (Temperature control unit) Master station (PLC)
[Remote input]
Address Details
RX(n+3)0
CH6 Second alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+3)1
CH6 Burnout alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+3)2
CH6 Heater break alarm (HBA) status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+3)3
CH6 PID/AT transfer status (OFF: PID control, ON: AT <Autotuning> )
RX(n+3)4
CH7 First alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+3)5
CH7 Second alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+3)6
CH7 Burnout alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+3)7
CH7 Heater break alarm (HBA) status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+3)8
CH7 PID/AT transfer status (OFF: PID control, ON: AT <Autotuning> )
RX(n+3)9
CH8 First alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+3)A
CH8 Second alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+3)B
CH8 Burnout alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+3)C
CH8 Heater break alarm (HBA) status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+3)D
CH8 PID/AT transfer status (OFF: PID control, ON: AT <Autotuning> )
RX(n+3)E
Unused
RX(n+3)F
Unused
RX(n+4)0
CH9 First alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)1
CH9 Second alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)2
CH9 Burnout alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)3
CH9 Heater break alarm (HBA) status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)4
CH9 PID/AT transfer status (OFF: PID control, ON: AT <Autotuning> )
RX(n+4)5
CH10 First alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)6
CH10 Second alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)7
CH10 Burnout alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)8
CH10 Heater break alarm (HBA) status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)9
CH10 PID/AT transfer status (OFF: PID control, ON: AT <Autotuning> )
RX(n+4)A
CH11 First alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)B
CH11 Second alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)C
CH11 Burnout alarm status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)D
CH11 Heater break alarm (HBA) status (OFF: Alarm OFF, ON: Alarm ON)
RX(n+4)E
CH11 PID/AT transfer status (OFF: PID control, ON: AT <Autotuning> )
RX(n+4)F
CH12 First alarm status (OFF: Alarm OFF, ON: Alarm ON)
Continued on the next page.