Instruction manual

6. REMOTE INPUT/OUTPUT AND REMOTE REGISTERS
IMSRM52-E5
33
6.2 Remote Input/Output
Remote input (RX) and output (RY) are ON/OFF data. Remote data corresponds to bit data, and
16-bit data is collectively (word) processed during FROM/TO instruction execution.
“n” in the table is the address assigned to the master station by the station No. setting.
It can be calculated by the following equation:
n = (Station No.
1) × 2
As the calculation result is expressed in decimal digits it is converted to hexadecimal digits
before substituted for “n” in the table.
Example: If the station No. of the H-LNK-A module is “1” or “5”
For station No. 1: Remote input RXn0 to RX(n+7)F RX00 to RX7F
Remote output RYn0 to RY(n+7)F RY00 to RY7F
For station No. 5: Remote input RXn0 to RX(n+7)F RX80 to RXFF
Remote output RYn0 to RY(n+7)F RY80 to RYFF
List of remote input (4 stations occupied, Temperature control 16 channels)
Direction: Remote device station (Temperature control unit) Master station (PLC)
Address Details
RXn0
CH1 First alarm status (OFF: Alarm OFF, ON: Alarm ON)
RXn1
CH1 Second alarm status (OFF: Alarm OFF, ON: Alarm ON)
RXn2
CH1 Burnout alarm status (OFF: Alarm OFF, ON: Alarm ON)
RXn3
CH1 Heater break alarm (HBA) status (OFF: Alarm OFF, ON: Alarm ON)
RXn4
CH1 PID/AT transfer status (OFF: PID control, ON: AT <Autotuning> )
RXn5
CH2 First alarm status (OFF: Alarm OFF, ON: Alarm ON)
RXn6
CH2 Second alarm status (OFF: Alarm OFF, ON: Alarm ON)
RXn7
CH2 Burnout alarm status (OFF: Alarm OFF, ON: Alarm ON)
RXn8
CH2 Heater break alarm (HBA) status (OFF: Alarm OFF, ON: Alarm ON)
RXn9
CH2 PID/AT transfer status (OFF: PID control, ON: AT <Autotuning> )
RXnA
Unused
RXnB
Unused
RXnC
Extended display completion *
RXnD
Extended setting completion *
RXnE
Unused
RXnF
Hardware error flag
1
* For details, refer to 6.5 Flag Operation (P. 51).
1
If hardware error (SR Mini HG error code) occurs: Turned on.
Continued on the next page.