Instruction manual

5. PREPARATION BEFORE OPERATION
IMSRM52-E5
29
5.2 Transmission Speed Setting
Set the transmission speed between the control unit (H-LNK-A module) and Control &
Communication Link master station using the transmission speed setting switch at the rear of the
H-LNK-A module. To do this, use a small blade screwdriver.
Set the same transmission speed to the Control & Communication Link master
station and all the H-LNK-A modules on the same line. Otherwise, a normal data link
cannot be made.
Setting procedure
1. To separate the module mainframe from the mother block, press the bottom on the module, lifting
upward, to release connection.
2. Set the transmission speed using the transmission speed setting switch at the rear of the
H-LNK-A module.
z To prevent electric shock or instrument failure, always turn off the power
before setting the switch.
z To prevent electric shock or instrument failure, never touch any section other
than those instructed in this manual.
WARNING
!
Press bottom of module and lift upward to release
Mother block
Module mainframe
Upper
section
Mother block
Module mainframe
Lowe
r
section
Setting range: 0 to 4
(Factory set value: 0)
0: 156 Kbps
1: 625 Kbps
2: 2.5 Mbps
3: 5 Mbps
4: 10 Mbps
5 to 9: Setting inhibited
Transmission speed
setting switch
H-LNK-A module
(Rear)