Instruction manual

4. WIRING
IMSRM52-E5
24
Terminal configuration
Use the solderless terminal appropriate to the screw size. If solderless terminal lugs are
used, a terminal cover is not kept.
Screw size: M3 × 7
Recommended tightening torque: 0.4 Nm [4 kgfcm]
Applicable wire: Solid/twisted wire of 0.25 to 1.65 mm
2
Specified solderless terminals:
Manufactured by J.S.T MFG CO., LTD.
Circular terminal with isolation V1.25MS3
Make sure that during field wiring parts of conductors can not come into contact with
adjacent conductive parts.
z Power supply voltage
Use a power supply is within the power supply voltage variation range.
21.6 to 26.4 V DC [Power supply voltage range] (Rating: 24 V DC)
z Ground
Ground the module using grounding wire with a cross section area of 2.0 mm
2
or more.
V1.253
φ3.2 MIN
φ5.5 MAX
φ3.2
4 mm
9.0 mm
Terminal Screws
Screw size: M3
Recommended tightening torque: 0.4 Nm (4 kgfcm)
FAIL
OUT1
NO
NO
NO
1
2
3
OUT2
4
5
6
11
12
13
14
15
1
2
3
4
5
6
7
8
9
10
DC
24V
OUT3
NO
NO
7
OUT4
8
9
OUT1
3
OUT2
4
5
6
OUT3
7
OUT4
8
9
+
-
+
-
+
-
+
-
+
-
10 10
12
13
14
FAIL output terminals
Open collector
output
Relay contact
output
Unused
Ground terminal
Unused
Power supply
terminals
Digital output
terminals
15
11