Instruction manual
2. SPECIFICATIONS
IMSRM52-E5
11
(4) Output
Item Specifications
FAIL output Relay contact output
Number of output points: 1 point
Rating: 250 V AC, 0.1 A (Resistive load)
CE/UL/cUL (or CSA) approved instrument:
30 V DC, 0.1 A
Electrical life: 300,000 time or more (Rated load)
Contact type: 1a contact
Failure action: Open at error occurrence
Digital output Relay contact output
Number of output points: 4 point
Rating: 250 V AC, 0.1 A (Resistive load)
CE/UL/cUL (or CSA) approved instrument:
30 V DC, 0.1 A
Electrical life: 300,000 time or more (Rated load)
Contact type: 1a contact
Open collector output
Number of output points: 4 points
Rating: 12 to 24 V DC
Maximum load current: 0.1 A/point, 0.8 A/common
Specify either relay contact output or open-collector output when
ordering.
Digital output can be selected from among the following outputs.
− Temperature alarm (First alarm, Second alarm)
− Heater break alarm (HBA)
− Burnout alarm
− Loop break alarm (LBA)
− Temp. rise completion
(5) Interface (RKC standard communication)
Item Specifications
Communication interface Based on RS-422A, EIA standard
Based on RS-232C, EIA standard
Specify when ordering
Communication method 4-wire system, multi-drop connection (RS-422A)
Point-to-point connection (RS-232C)
Protocol Based on ANSI X 3.28 subcategory 2.5, B1
Synchronous method Star
t
-stop synchronous type
Communication speed 2400 bps, 4800 bps, 9600 bps, 19200 bps
Any can be selected.
Data bit configuration Start bit: 1
Data bit: 7 or 8
Parity bit: Without, Odd or Even (For 8 data bits: Without)
Stop bit: 1
Error control Vertical parity (When parity bit is selected)
Horizontal parity
Data types ASCII code