Instruction manual

2. SPECIFICATIONS
IMSRM52-E5
11
(4) Output
Item Specifications
FAIL output Relay contact output
Number of output points: 1 point
Rating: 250 V AC, 0.1 A (Resistive load)
CE/UL/cUL (or CSA) approved instrument:
30 V DC, 0.1 A
Electrical life: 300,000 time or more (Rated load)
Contact type: 1a contact
Failure action: Open at error occurrence
Digital output Relay contact output
Number of output points: 4 point
Rating: 250 V AC, 0.1 A (Resistive load)
CE/UL/cUL (or CSA) approved instrument:
30 V DC, 0.1 A
Electrical life: 300,000 time or more (Rated load)
Contact type: 1a contact
Open collector output
Number of output points: 4 points
Rating: 12 to 24 V DC
Maximum load current: 0.1 A/point, 0.8 A/common
Specify either relay contact output or open-collector output when
ordering.
Digital output can be selected from among the following outputs.
Temperature alarm (First alarm, Second alarm)
Heater break alarm (HBA)
Burnout alarm
Loop break alarm (LBA)
Temp. rise completion
(5) Interface (RKC standard communication)
Item Specifications
Communication interface Based on RS-422A, EIA standard
Based on RS-232C, EIA standard
Specify when ordering
Communication method 4-wire system, multi-drop connection (RS-422A)
Point-to-point connection (RS-232C)
Protocol Based on ANSI X 3.28 subcategory 2.5, B1
Synchronous method Star
t
-stop synchronous type
Communication speed 2400 bps, 4800 bps, 9600 bps, 19200 bps
Any can be selected.
Data bit configuration Start bit: 1
Data bit: 7 or 8
Parity bit: Without, Odd or Even (For 8 data bits: Without)
Stop bit: 1
Error control Vertical parity (When parity bit is selected)
Horizontal parity
Data types ASCII code