Instruction manual

10 IMSRM52-E5
2. SPECIFICATIONS
2.1 H-PCP-G Module
(1) Basic functions
Item Specifications
Data supervision function Operating data/system data
Unit diagnosis function Function modules configuration check
Sel
f
-diagnostic function Check ite
ROM/RAM check
Watchdog timer
CPU power supply monitoring
Operation at erro
r
occurrence in
self-diagnosis
All module outputs are set to the off state
hardware wise.
Memory backup function RAM is backed up by lithium battery.
Data retaining time: Approx. 10 years
(Time integrated during power off)
Control & Communication
Link connectable modules
H-TIO-A/B/C/D/E/F/G/H/J/P/R
H-CT-A
H-LNK-A
Number of temperature control channels:
Up to 16 channels/control unit
Number of connectable modules: 8 modules/control unit
(Excluding H-LNK-A)
Operation afte
r
power on Star
t
-up from control STOP condition (Factory set value)
Can be changed by the host computer communication setting
(Initialize setting).
(2) Power input
Item Specifications
Power supply voltage Rating: 24 V DC
Range of power supply
voltage
21.6 to 26.4 V DC
Power consumption 21 W max.
Surge current 30 A or less
(3) Power output (Function module power)
Item Specifications
Output voltage/current 5 V DC, 1.7 A max.
12 V DC, 1.0 A max.
Must be used within the maximum power consumption value.
Overcurrent protection Fold-
b
ack limiting method: 5V