Instruction manual
6. RKC COMMUNICATION
IMS01J02-E1
84
Continued from the previous page.
Name
Iden-
tifier
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set
value
ON/OFF control
differential gap (upper)
[H-TIO-, H-CIO-A,
H-SIO-A]
IV
6 R/W C 0.00 to 10.00 % of span 0.02
ON/OFF control
differential gap (lower)
[H-TIO-, H-CIO-A,
H-SIO-A]
IW
6 R/W C 0.00 to 10.00 % of span 0.02
Manipulated output
value at input error
[H-TIO-, H-CIO-A,
H-SIO-A]
OE
6 R/W C
−5.0 to +105.0 %
(Heat control, Position
proportioning control and
Speed control)
−105.0 to +105.0 %
(Heat/cool control)
0.0
Output change rate
limiter (up)
[H-TIO-, H-CIO-A,
H-SIO-A]
PH
6 R/W C
0.0 to 100.0 %/second
(0.0: OFF)
Setting will be invalid in
ON/OFF control.
0.0
Output change rate
limiter (down)
[H-TIO-, H-CIO-A,
H-SIO-A]
PL
6 R/W C
0.0 to 100.0 %/second
(0.0: OFF)
Setting will be invalid in
ON/OFF control.
0.0
Direct/Reverse action
selection
[H-TIO-, H-CIO-A,
H-SIO-A]
XE
1 R/W C
0: Direct action
1: Reverse action
If the Direct/Reverse action
selection is changed, all of
the settings corresponding to
the channels in the relevant
module return to the default
values.
Setting will be invalid in
heat/cool control.
The factory
set value
varies
depending
on the
specifications
when
ordering.
Continued on the next page.