Instruction manual
6. RKC COMMUNICATION
IMS01J02-E1
83
Continued from the previous page.
Name
Iden-
tifier
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set
value
AW
6 R/W C
TC/RTD input:
Within input range
Input range
(low)
Input error
determination point
(low)
[H-TIO-, H-CIO-A,
H-SIO-A]
Current/voltage input,
H-SIO-A:
Within display scale range
Display
scale low
Action at input error
(high)
[H-TIO-, H-CIO-A,
H-SIO-A]
WH
1 R/W C
0: Normal control
1: Manipulated output value at
input error
0
a
Action at input error
(low)
[H-TIO-, H-CIO-A,
H-SIO-A]
WL
1 R/W C
0: Normal control
1: Manipulated output value at
input error
0
AT bias
[H-TIO-, H-CIO-A,
H-SIO-A]
GB
6 R/W C
Within ± input span range
0
b
Output limiter (high)
[For heat/cool control:
Heat-side output limiter
(high)]
[H-TIO-, H-CIO-A,
H-SIO-A]
OH
6 R/W C
[Heat control, Position
proportioning control and
Speed control]
Output limiter (low) to
105.0 %
[Heat/cool control]
Heat-side output limiter
(high): −5.0 % to +105.0 %
Heat-side output limiter
(low): −5.0 % (fixed)
100.0
c
Output limiter (low)
[For heat/cool control:
Cool-side output limiter
(high)]
[H-TIO-, H-CIO-A,
H-SIO-A]
OL
6 R/W C
[Heat control, Position
proportioning control and
Speed control]
−5.0 % to Output limiter
(high)
[Heat/cool control]
Cool-side output limiter
(high): −5.0 % to +105.0 %
Cool-side output limiter
(low): −5.0 % (fixed)
0.0
d
a
Heat control (H-TIO-/H-CIO-A): 0 Heat/cool control (H-TIO-/H-CIO-A): 1
Position proportioning control (H-TIO-K): 0 Speed control (H-SIO-A): 0
b
The position of the decimal point differs depending on the input range.
c
Heat control (H-TIO-/H-CIO-A): 100.0 Heat/cool control (H-TIO-/H-CIO-A): 100.0
Position proportioning control (H-TIO-K): 100.0 Speed control (H-SIO-A): 100
d
Heat control (H-TIO-/H-CIO-A): 0.0 Heat/cool control (H-TIO-/H-CIO-A): 100.0
Position proportioning control (H-TIO-K): 0.0 Speed control (H-SIO-A): 0
Continued on the next page.