Instruction manual

6. RKC COMMUNICATION
IMS01J02-E1
82
Name
Iden-
tifier
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set
value
Input range number
[H-TIO-, H-CIO-A,
H-SIO-A]
XI
6 R/W C
H-TIO-A/B/C/D/K/P:
0 to 63
H-TIO-E/F/G/R, H-CIO-A:
0 to 120
H-TIO-H/J, H-CIO-A:
0 to 12
H-SIO-A: 0 (Fixed)
If the input range number is
changed, all of the settings
corresponding to the channels
in the relevant module return to
the default values.
See Input range table (P. 107)
The factory
set value
varies
depending
on the
specifications
when
ordering.
Setting limiter (high)
[H-TIO-, H-CIO-A,
H-SIO-A]
SH
6 R/W C
TC/RTD input:
Setting limiter (low) to
Input range (high)
Input range
(high)
Current/voltage input,
H-SIO-A:
Setting limiter (low) to
Display scale high
Display
scale high
Setting limiter (low)
[H-TIO-, H-CIO-A,
H-SIO-A]
SL
6 R/W C
TC/RTD input:
Input range (low) to
Setting limiter (high)
Input range
(low)
Current/voltage input,
H-SIO-A:
Display scale low to
Setting limiter (high)
Display
scale low
Digital filter
[H-TIO-, H-CIO-A,
H-SIO-A]
F1
6 R/W C
H-TIO-A/B/C/D/K/P
0 to 100 seconds (0: OFF)
H-TIO-E/F/G/H/J/R,
H-CIO-A, H-SIO-A
0.0 to 100.0 seconds
(0.0: OFF)
0 or 0.0
AV
6 R/W C
TC/RTD input:
Within input range
Input range
(high)
Input error
determination point
(high)
[H-TIO-, H-CIO-A,
H-SIO-A]
Current/voltage input,
H-SIO-A:
Within display scale range
Display
scale high
Continued on the next page.