Instruction manual
6. RKC COMMUNICATION
IMS01J02-E1
73
Continued from the previous page.
Name
Iden-
tifier
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set
value
Control loop break
alarm (LBA) status
[H-TIO-, H-CIO-A]
AP
1 RO C 0: OFF 1: ON
LBA use selection
[H-TIO-, H-CIO-A]
HP
1 R/W C 0: Unused 1: Used 0
LBA time
[H-TIO-, H-CIO-A]
C6
6 R/W C 1 to 7200 seconds 480
LBA deadband
[H-TIO-, H-CIO-A]
V2
6 R/W C Input span 0
a
AO output value
monitor
[H-AO-A/B]
M6
6 RO C
Display scale range
b
Data will be valid in manual
mode.
AO output set value
[H-AO-A/B]
S6
6 R/W C
Display scale range
b
Setting will be valid in manual
mode.
0.0
AO function selection
[H-AO-A/B]
XO
6 R/W C
0: Unused
1: Manual mode (outputs data
given by the AO output set
value)
2: Temperature measured value
(PV)
3: Set value monitor
4: Temperature deviation value
(deviation between the
temperature measured value
and set value monitor)
5: Heat-side manipulated
output value
6: Cool-side manipulated
output value
7: AI measured value
8: TI measured value
9: Opening monitor
(2 to 9: Recorder output mode)
1
a
The position of the decimal point differs depending on the input range.
b
The position of the decimal point differs depending on AO decimal point position (Identifier JR)
setting.
Continued on the next page.