Instruction manual
6. RKC COMMUNICATION
IMS01J02-E1
72
Continued from the previous page.
Name
Iden-
tifier
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set
value
Temperature rise
completion trigger
1
[H-TIO-, H-CIO-A]
HS
1 R/W C
0: Unused 1: Used
Do not set “1: Used” in
H-TIO-H/J module and
H-SIO-A module, because
temperature rise completion is
not judged.
0
Temperature rise
completion soak time
[H-TIO-, H-CIO-A]
T3
6 R/W U 0 to 360 minutes 0
AI measured value
[H-AI-A/B]
M5
6 RO C Within display scale range
2
AI alarm 1 status
[H-AI-A/B]
AD
1 RO C 0: OFF 1: ON
AI alarm 2 status
[H-AI-A/B]
AE
1 RO C 0: OFF 1: ON
AI alarm 1 set value
[H-AI-A/B]
A5
6 R/W C Within display scale range
2
Process high
alarm: 100.0
Process low
alarm: 0.0
No alarm
function:
100.0
AI alarm 2 set value
[H-AI-A/B]
A6
6 R/W C Within display scale range
2
Process high
alarm: 100.0
Process low
alarm: 0.0
No alarm
function: 0.0
AI zero point correction
[H-AI-A/B]
JI
1 R/W C 0: Cancel 1: Execution 0
AI full scale correction
[H-AI-A/B]
JJ
1 R/W C 0: Cancel 1: Execution 0
AI operation mode
transfer
[H-AI-A/B]
NJ
1 R/W C
0: Unused mode
Neither monitor nor alarm
monitor is done in this mode.
1: Normal mode
Normal mode in which
monitor and alarm are done.
1
1
If the channel of each of the H-TIO-H/J and H-SIO-A modules is set “1: Used,” it does no reach the
completion of temperature rise. As a result, the state of this completion (Identifier HE) which is judged
by performing the OR operation of all the channels cannot be attained, thereby continuing the
incompletion of temperature rise.
2
The position of the decimal point differs depending on AI decimal point position (Identifier JU)
setting.
Continued on the next page.