Instruction manual
6. RKC COMMUNICATION
IMS01J02-E1
70
Continued from the previous page.
Name
Iden-
tifier
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set
value
Operation mode transfer
[H-TIO-, H-CIO-A,
H-SIO-A]
EI
1 R/W C
0: Unused
If set to “Unused,” no control,
monitor or alarm monitor is
performed.
1: Monitor
If set to “Monitor,” only the
monitor is performed. No
control or alarm monitor is
performed.
2: Alarm
If set to “Alarm,” monitor or
alarm monitor is performed.
No control is performed.
3: Normal
Selected to normal mode to
perform control, monitor or
alarm monitor.
3
Heat-side proportioning
cycle time
[H-TIO-, H-CIO-A]
T0
6 R/W C
1 to 100 seconds
Setting will be invalid in
current/voltage output.
20
a
Cool-side proportioning
cycle time
[H-TIO-, H-CIO-A]
T1
6 R/W C
1 to 100 seconds
Setting will be invalid in
current/voltage output and heat
control.
20
a
PV bias
[H-TIO-, H-CIO-A,
H-SIO-A]
PB
6 R/W C
−5.00 to +5.00 % of span
ZK-1103 specification:
−Input span to +Input span
b
0.00
ZK-1103:
0
c
Control RUN/STOP
transfer
[H-PCP-J]
SR
1 R/W U
0: Control STOP
1: Control RUN
Only when the initial set mode
is “0: Normal communication,”
control can be start.
0
a
Relay contact output: 20 seconds
Voltage pulse output, Open collector output, Triac output: 2 seconds
b
For −Input span < −999.9 ....... Low limit value: −999.9
For −Input span < −99.99 ....... Low limit value: −99.99
For −Input span < −9.999 ....... Low limit value: −9.999
c
Unit (°C, °F, etc.) and decimal point position (No decimal place, One decimal place, Two decimal
places or Three decimal places) depends on input range type.
Continued on the next page.