Instruction manual

6. RKC COMMUNICATION
IMS01J02-E1
69
Continued from the previous page.
Name
Iden-
tifier
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set
value
Alarm 1 set value
[H-TIO-, H-CIO-A,
H-SIO-A]
A1
6 R/W C
Alarm 2 set value
[H-TIO-, H-CIO-A,
H-SIO-A]
A2
6 R/W C
TC/RTD input:
Within input range or span
range
Current/voltage input,
H-SIO-A:
Within display scale range
or span range
See Factory
set value
table of
Alarm 1/
Alarm 2
set value *
Setting change rate
limiter
[H-TIO-, H-CIO-A,
H-SIO-A]
HH
6 R/W C
0.0 to 100.0 % of
span/minute
0.0
Heater break alarm set
value 1
[H-TIO-A/C/D]
A3
6 R/W C
0.0 to 100.0 A or
0.0 to 30.0 A
For the current transformer
(CT) input of the
H-TIO-A/C/D module.
0.0
Heater break alarm set
value 2
[H-CT-A]
A4
6 R/W C
0.0 to 100.0 A or
0.0 to 30.0 A
For the current transformer
(CT) input of the H-CT-A
module.
0.0
* Factory set value table of Alarm 1/Alarm 2 set value
Input type Alarm type Alarm 1 set value Alarm 2 set value
TC/RTD input
Process high alarm Input range (high limit) Input range (high limit)
Process low alarm Input range (low limit) Input range (low limit)
Deviation high alarm, Deviation
high/low alarm, Band alarm
50 °C 50 °C
Deviation low alarm
50 °C 50 °C
No alarm function Input range (high limit) Input range (low limit)
Current/voltage input
Process high alarm 100.0 % 100.0 %
Process low alarm 0.0 % 0.0 %
Deviation high alarm, Deviation
high/low alarm, Band alarm
50 % 50 %
Deviation low alarm
50 % 50 %
No alarm function 100.0 % 0.0 %
Continued on the next page.