Instruction manual

5. SETTINGS BEFORE OPERATION
IMS01J02-E1
49
5.3 Start-up Procedures
Check prior to power on
Check the following items before turning on the power to the control unit.
Operation environments conform to 3.1 Mounting Cautions (P. 20).
Wiring and connections conform to 4. WIRING (P. 25).
Power supply voltage conforms to 2. SPECIFICATIONS (P. 14).
Check after power on
Check that the RUN lamps on the H-PCP-J and function modules are flashing.
Operation after power on
Action after power on differs depending on control RUN/STOP holding (Identifier X1) setting.
Status after power-ON
Control RUN/STOP
holding
(Identifier X1)
Operation mode Control RUN/STOP
0: Not hold Same as mode before the power
failure
“0: Control STOP”
Stopped until “1: Control RUN”
is instructed from the PLC or host
computer.
1: Hold Same as mode before the power
failure
Same as status before the power
failure
Control before power failure is
maintained even if no PLC or
host computer is connected.
2: Start-up from control run
status
“1: Monitor” mode
However if the operation mode is
set to “0: Unused,” “0: Unused”
remains unchanged.
“1: Control RUN”
However, no control is performed
until the operation mode is set to
“3: Normal (perform control).”
For the control RUN/STOP holding (Identifier X1), see the 6.3 Initial Settings (P. 81).