Instruction manual

5. SETTINGS BEFORE OPERATION
IMS01J02-E1
46
COM.PORT3 setting switch (SW3)
SW3
1 2
Data bit configuration
OFF OFF
Data 8-bit, Without parity, Stop 1-bit
ON OFF
Data 7-bit, Odd parity, Stop 1-bit
OFF ON
Data 7-bit, Even parity, Stop 1-bit
ON ON
Data 7-bit, Even parity, Stop 2-bit
Factory set value: Data 8-bit, Without parity, Stop 1-bit
SW3
3 4
Communication speed
OFF OFF
9600 bps
ON OFF
19200 bps
OFF ON
38400 bps
ON ON
Don't set this one
Factory set value: 9600 bps
SW3
5
Protocol
OFF
RKC communication protocol
(Based on ANSI X3.28 subcategory 2.5 B1)
See 6. RKC COMMUNICATION (P. 52).
ON
Modbus protocol
See 7. MODBUS (P. 109).
Factory set value: RKC communication protocol
SW3
6
Initialize
OFF Normal (It is initialized only in initialization execution)
ON In power on, all module is initialized
Factory set value: Normal (It is initialized only in initialization execution)
Continued on the next page.