2. SPECIFICATIONS
IIMS01J02-E1
18
COM.PORT3
Interface: Based on RS-232C, EIA standard
Based on RS-422A, EIA standard
Based on RS-485, EIA standard
Specify when ordering
Connection method: RS-232C: Point-to-point connection
RS-422A: 4-wire system, multi-drop connection
RS-485: 2-wire system, multi-drop connection
Protocol: • Based on ANSI X3.28 subcategory 2.5 B1 (RKC communication)
Error control: Vertical parity (when parity bit is selected)
Horizontal parity
Data types: ASCII 7-bit code
• Modbus protocol
Signal transmission mode: Remote Terminal Unit (RTU) mode
Function codes: 03H Read holding registers
06H Preset single register
08H Diagnostics (loopback test)
10H Preset multiple registers
Error check method: CRC-16
Error codes: 1: Function code error (An unsupported
function code was specified)
2: − When written to read only data
− When any address other than 0000H
to 02EEH is specified (However,
07D0H to 0BB7H are excluded)
3: − When the data written exceeds the
setting range
− When the specified number of data
items in the query message exceeds
the maximum number of data items
available
Protocol can be selected with switch
Synchronous method: Start/stop synchronous type
Communication speed: 9600 bps, 19200 bps, 38400 bps
Communication speed can be selected with switch
Data bit configuration: Start bit: 1
Data bit: 7 or 8
Parity bit: Without, Odd or Even
Without for 8 data bits
Stop bit: 1 or 2
Data bit configuration can be selected with switch
Connected equipment: Host computer, touch panel or operation panel