2. SPECIFICATIONS
IIMS01J02-E1
15
Digital output
Number of outputs: 8 points
Output type: Open collector output
Number of common points: Vcc: 2 points, GND: 2 points (8 points/common)
Isolation method: Photocoupler isolation
Load voltage: 12 to 24 V DC
Maximum load current: 0.1 A/point, 0.8 A/common
Output data: Digital output can be selected from the following:
− Temperature alarm (Alarm 1, Alarm 2)
− Heater break alarm (HBA)
− Burnout
− TI Alarm (Alarm 1, Alarm 2)
− AI Alarm (Alarm 1, Alarm 2)
− Control loop break alarm (LBA)
− Temperature rise completion
− Temperature rise completion
− FAIL output
− PLC communication status
− Unused