Instruction manual

7. MODBUS
IMS01J02-E1
165
(8) H-AO-A/B module data
Address CH Name
157CH (5500) CH1
AO output value
monitor
H-AO-A/B
15A3H (5539) CH160
15A4H (5540) CH1 AO output set value
H-AO-A/B
15CBH (5579) CH160
15CCH (5580) CH1 AO function selection
H-AO-A/B
15F3H (5619) CH160
15F4H (5620) CH1 AO corresponding channel setting
H-AO-A/B
161BH (5659) CH160
161CH (5660) CH1 AO zooming high limit
H-AO-A/B
1643H (5699) CH160
1644H (5700) CH1 AO zooming low limit
H-AO-A/B
166BH (5739) CH160
166CH (5740) CH1 AO zero point correction
H-AO-A/B
1693H (5779) CH160
1694H (5780) CH1 AO full scale correction
H-AO-A/B
16BBH (5819) CH160
16BCH (5820) CH1 AO display scale high
H-AO-A/B
16E3H (5859) CH160
16E4H (5860) CH1 AO display scale low
H-AO-A/B
170BH (5899) CH160
170CH (5900) CH1 AO decimal point position
H-AO-A/B
1733H (5939) CH160
1734H (5940) CH1 AO output change rate limiter
H-AO-A/B
175BH (5979) CH160
175CH (5980)
Do not use this address range
176FH (5999)