Instruction manual
7. MODBUS
IMS01J02-E1
155
7.4.2 Data map list
(1) Read only data
Address CH Name
0000H ( 0) CH1
Temperature measured value (PV)
⋅
⋅
⋅
⋅
⋅
⋅
H-TIO-, H-CIO-A
⋅
⋅
⋅
⋅
⋅
⋅
Motor speed measured value
0013H ( 19) CH20
H-SIO-A
0014H ( 20) CH1 Heat-side manipulated output value
⋅
⋅
⋅
⋅
⋅
⋅
H-TIO-, H-CIO-A, H-SIO-A
0027H ( 39) CH20
0028H ( 40) CH1 Cool-side manipulated output value
⋅
⋅
⋅
⋅
⋅
⋅
H-TIO-, H-CIO-A, H-SIO-A
003BH ( 59) CH20
003CH ( 60) CH1 Current transformer input measured value 1
⋅
⋅
⋅
⋅
⋅
⋅
H-TIO-A/C/D
004FH ( 79) CH20
0050H ( 80) CH1 Current transformer input measured value 2
⋅
⋅
⋅
⋅
⋅
⋅
H-CT-A
0063H ( 99) CH20
0064H ( 100) CH1 Status
⋅
⋅
⋅
⋅
⋅
⋅
H-TIO-, H-CIO-A, H-SIO-A
0077H ( 119) CH20
0078H ( 120)
Temperature rise completion status
(for each control unit)
H-TIO-, H-CIO-A
0079H ( 121)
Error code
(for each control unit)
H-PCP-J
007AH ( 122)
Overall alarm status
(for each control unit)
H-PCP-J
007BH ( 123)
⋅
⋅
⋅
Do not use this address range
008BH ( 139)
008CH ( 140) CH1 Set value monitor
⋅
⋅
⋅
⋅
⋅
⋅
H-TIO-, H-CIO-A, H-SIO-A
009FH ( 159) CH20
00A0H ( 160) CH21 Current transformer input measured value 2
⋅
⋅
⋅
⋅
⋅
⋅
H-CT-A
00C7H ( 199) CH60