Instruction manual
7. MODBUS
IMS01J02-E1
132
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
Cascade ON/OFF
[H-CIO-A]
R/W C
0: OFF 1: ON
Setting will be valid in master channel.
0
Cascade gain
[H-CIO-A]
R/W C
−9.999 to +10.000
As the cascade gain is valid only in the slave
channel, the polling or selecting of the same
value is made also in the master channel.
1.000
Cascade bias
[H-CIO-A]
R/W C
−99.99 to +100.00 %
As the cascade bias is valid only in the slave
channel, the polling or selecting of the same
value is made also in the master channel.
−50.00
Positioning output
neutral zone
[H-TIO-K]
R/W C
0.1 to 10.0 % of motor time
2.0
Motor time
[H-TIO-K]
R/W C
5 to 1000 seconds
10
Integrated output limiter
[H-TIO-K]
R/W C
100.0 to 200.0 % of motor time
150.0
Manual positioning
output value
[H-TIO-K]
R/W C
−5.0 to +105.0 %
0.0
Setting change rate
limiter
[H-TIO-, H-CIO-A,
H-SIO-A]
R/W C
0.0 to 100.0 % of span/minute
0.0
Output limiter (high)
[For heat/cool control:
Heat-side output limiter
(high)]
[H-TIO-, H-CIO-A,
H-SIO-A]
R/W C
[Heat control, Position proportioning control
and Speed control]
Output limiter (low) to 105.0 %
[Heat/cool control]
Heat-side output limiter (high):
−5.0 % to +105.0 %
Heat-side output limiter (low):
−5.0 % (fixed)
100.0 *
* Heat control (H-TIO-/H-CIO-A): 100.0 Heat/cool control (H-TIO-/H-CIO-A): 100.0
Position proportioning control (H-TIO-K): 100.0 Speed control (H-SIO-A): 100
Continued on the next page.