Instruction manual
7. MODBUS
IMS01J02-E1
130
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
Heat-side proportioning
cycle time
[H-TIO-, H-CIO-A]
R/W C
1 to 100 seconds
Setting will be invalid in current/voltage
output.
20
a
Cool-side proportioning
cycle time
[H-TIO-, H-CIO-A]
R/W
C
1 to 100 seconds
Setting will be invalid in current/voltage
output and heat control.
20
a
Auto/Manual transfer
[H-TIO-, H-CIO-A]
R/W C
0: Auto 1: Manual
Setting will be invalid in ON/OFF control
and heat/cool control.
0
Manual output value
[H-TIO-, H-CIO-A]
R/W
C
−5.0 to +105.0 %
Setting will be invalid in ON/OFF control
and heat/cool control.
−105.0 to +105.0 %
H-TIO-C/D [Z-1017 specification] :
−105.0 to 0.0 % (cool-side)
0.0 to +105.0 % (heat-side)
0.0
LBA use selection
[H-TIO-, H-CIO-A]
R/W C
0: Unused 1: Used
0
LBA time
[H-TIO-, H-CIO-A]
R/W
C
1 to 7200 seconds
480
LBA deadband
[H-TIO-, H-CIO-A]
R/W C
Input span
0
b
PV bias
[H-TIO-, H-CIO-A,
H-SIO-A]
R/W C
−5.00 to +5.00 % of span
ZK-1103 specification:
−Input span to +Input span
0.00
ZK-1103:
0
c
Temperature rise
completion range
[H-TIO-, H-CIO-A]
R/W C
1 to 10 °C or 1 to 20 °F
b
10 or 20
b, d
a
Relay contact output: 20 seconds
Voltage pulse output, Open collector output, Triac output: 2 seconds
b
The position of the decimal point differs depending on the input range.
c
Unit (°C, °F, etc.) and decimal point position (No decimal place, One decimal place, Two decimal
places or Three decimal places) depends on input range type.
d
TC/RTD input: 10 °C or 20 °F
Current/voltage input: 10 % of display scale
Continued on the next page.