Instruction manual

7. MODBUS
IMS01J02-E1
124
7.3.3 Communication data list
Name
: Item stored in the memory area.
[ ]: The functional module name that data becomes valid is written.
Attributes
RO: Read only Slave (SR Mini HG SYSTEM) Master
R/W: Read and Write Slave (SR Mini HG SYSTEM) Master
WO: Write only Slave (SR Mini HG SYSTEM) Master
Structure
C: Data for each channel L: Data for each event input logic circuit
M: Data for each module U: Data for each unit address
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
Temperature measured
value (PV)
[H-TIO-, H-CIO-A]
RO C
TC/RTD input:
Within input range
Current/voltage input:
Within display scale range
Motor speed measured
value
[H-SIO-A]
RO C
Within display scale range
Heat-side manipulated
output value
[H-TIO-, H-CIO-A,
H-SIO-A]
RO C
0.5 to +105.0 %
Cool-side manipulated
output value
[H-TIO-, H-CIO-A]
RO C
0.5 to +105.0 %
Current transformer
input measured value 1
[H-TIO-A/C/D]
RO
C
0.0 to 100.0 A or 0.0 to 30.0 A
Current transformer (CT) input measured
value of the H-TIO-A/C/D module.
Current transformer
input measured value 2
[H-CT-A]
RO C
0.0 to 100.0 A or 0.0 to 30.0 A
Current transformer (CT) input measured
value of the H-CT-A module.
Continued on the next page.