Instruction manual
6. RKC COMMUNICATION
IMS01J02-E1
97
Continued from the previous page.
Name
Iden-
tifier
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set
value
Event DI type selection 1
[H-DI-B]
R1
6 R/W L
0 to 30 *
(17 to 30: Not settable)
0
Event DI type selection 2
[H-DI-B]
R2
6 R/W L
0 to 30 *
(17 to 30: Not settable)
0
Event DI type selection 3
[H-DI-B]
R3
6 R/W L
0 to 30 *
(17 to 30: Not settable)
0
Event DI type selection 4
[H-DI-B]
R4
6 R/W L
0 to 30 *
(17 to 30: Not settable)
0
Event DI corresponding
channel selection 1
[H-DI-B]
E1
6 R/W L 1 to 80 * 1
Event DI corresponding
channel selection 2
[H-DI-B]
E2
6 R/W L 1 to 80 * 1
Event DI corresponding
channel selection 3
[H-DI-B]
E3
6 R/W L 1 to 80 * 1
Event DI corresponding
channel selection 4
[H-DI-B]
E4
6 R/W L 1 to 80 * 1
Event DI reversal
selection 1
[H-DI-B]
W1
1 R/W L 0: Normal 1: Reversal 0
Event DI reversal
selection 2
[H-DI-B]
W2
1 R/W L 0: Normal 1: Reversal 0
Event DI reversal
selection 3
[H-DI-B]
W3
1 R/W L 0: Normal 1: Reversal 0
Event DI reversal
selection 4
[H-DI-B]
W4
1 R/W L 0: Normal 1: Reversal 0
Event DI logic circuit
selection
[H-DI-B]
LU
1 R/W L 0: AND (1 active)
1: NAND (0 active)
2: OR (1 active)
3: NOR (0 active)
0
Event DI delay timer
setting
[H-DI-B]
LW
6 R/W L 0 to 255 times 1
* Set the type and corresponding channel of Event DI. Event DI uses it with logic input function.
For the data , see the Logic input function (P. 105).