Instruction manual

6. RKC COMMUNICATION
IMS01J02-E1
94
Continued from the previous page.
Name
Iden-
tifier
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set
value
Event DO function
selection
[H-DO-C]
XF
6 R/W C 0 to 30 * 0
Event DO corresponding
channel setting
[H-DO-C]
XG
6 R/W C 1 to 40 * 1
Event DO mode select
setting
[H-DO-C]
XH
6 R/W C 0 to 40 * 0
Event DO extension
alarm differential gap
[H-DO-C]
HG
6 R/W U 0.00 to 10.00 % 0.10
Event DO extension
alarm interlock
[H-DO-C]
LE
1 R/W U 0: Not provided
1: Provided
0
Number of Event DO
extension alarm delay
times
[H-DO-C]
TI
6 R/W U 0 to 255 times 0
Cascade tracking
[H-CIO-A]
XL
1 R/W M
0: Not provided
Cascade monitored value
becomes zero.
1: Provided
Cascade monitored value
just before is hold.
0
Cascade data selection
[H-CIO-A]
KD
1 R/W M
0: Manipulated outpur value
1: Temperature measured
value (PV)
2: Temperature set value
(SV)
3: Set value monitor
4: Temperature deviation
0
* Set the function, corresponding channel and mode select of Event DO. Event DO uses it with event
output function.
For the data, see the Event output function (P. 101).
Continued on the next page.