Instruction manual

6. RKC COMMUNICATION
IMS01J02-E1
92
Continued from the previous page.
Name
Iden-
tifier
Digits
Attri-
bute
Struc-
ture
Data range
Factory
set
value
AI alarm 1 type
selection
[H-AI-A/B]
XC
1 R/W U
AI alarm 2 type
selection
[H-AI-A/B]
XD
1 R/W U
0: Process high alarm
1: Process low alarm
2 to 6: No alarm function
The factory
set value
varies
depending
on the
specifications
when
ordering.
AI alarm 1 hold action
[H-AI-A/B]
WC
1 R/W U
AI alarm 2 hold action
[H-AI-A/B]
WD
1 R/W U
0: Not provided
1: Provided
The factory
set value
varies
depending
on the
specifications
when
ordering.
AI alarm 1 interlock
[H-AI-A/B]
LC
1 R/W U
0: Not provided
1: Provided
0
AI alarm 2 interlock
[H-AI-A/B]
LD
1 R/W U
0: Not provided
1: Provided
0
Number of AI alarm
delay times
[H-AI-A/B]
TK
6 R/W U 0 to 255 times 0
AI decimal point
position
[H-AI-A/B]
JU
1 R/W C
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
1
Power supply frequency
selection
[H-PCP-J]
JT
1 R/W U 0: 50 Hz 1: 60 Hz 0
AI digital filter
[H-AI-A/B]
F2
6 R/W C
0.0 to 100.0 seconds
(0.0: OFF)
0.0
AI moving average
[H-AI-A/B]
VA
1 R/W C
0: Not provided
1: Provided
0
Continued on the next page.