Specifications

3. INITIALIZE COMMUNICATION DATA
IMR01H03-E4
48
Continued from the previous page.
Name Data range Factory set value Attri-
bute
Contact input logic
selection
0 to 9
See contact input logic tables
0R/W
Communication
protocol selection
0: RKC communication protocol
(Multi-point mode)
1: Modbus communication protocol
2: RKC communication protocol
(Single mode)
Factory set value
varies depending on
the instrument
specification.
R/W
RUN/STOP transfer
logic selection
0: 0 (STOP) 1 (RUN)
1: 0 (RUN) 1 (STOP)
0R/W
Contact input logic tables
Set value STOP selection Memory area
selection
Used/Unused of
DI SET terminal (No.43)
0 When contact input (RUN/STOP
transfer) opens, stop.
Memory area
transfer 1 to 8
Used
1 When contact input (RUN/STOP
transfer) opens, stop.
Memory area
transfer 1 to 8
Unused
2 When contact input (RUN/STOP
transfer) opens, stop.
Memory area
transfer 1 to 7
Used
3 When contact input (RUN/STOP
transfer) opens, stop.
Memory area
transfer 1 to 7
Unused
4 When contact input (RUN/STOP
transfer) opens, stop.
There is no
memory area
transfer function.
Unused
5 When contact input (RUN/STOP
transfer) is closed, stop.
Memory area
transfer 1 to 8
Used
6 When contact input (RUN/STOP
transfer) is closed, stop.
Memory area
transfer 1 to 8
Unused
7 When contact input (RUN/STOP
transfer) is closed, stop.
Memory area
transfer 1 to 7
Used
8 When contact input (RUN/STOP
transfer) is closed, stop.
Memory area
transfer 1 to 7
Unused
9 When contact input (RUN/STOP
transfer) is closed, stop.
There is no
memory area
transfer function.
Unused
For details of the selection item, see the 2.5 F24 Contact Input Specification (P. 22).