Specifications
3. INITIALIZE COMMUNICATION DATA
IMR01H03-E4
45
Continued from the previous page.
Name Data range Factory set value Attri-
bute
Alarm 3 type
selection
1
0: No alarm
1: SV high alarm
2: SV low alarm
3: Process high alarm
4: Process low alarm
5: Deviation high alarm
6: Deviation low alarm
7: Deviation high/low alarm
8: Band alarm
Factory set value
varies depending on
the instrument
specification.
R/W
Alarm 3 hold action
selection
2
0: Without alarm hold action
1: Effective when the power is turned on,
or operation is changed from STOP to
RUN.
2: Valid when:
• the power is turned on,
• operation is changed from STOP to
RUN,
• the SV is changed, or
• the memory area (control area) is
changed.
Without alarm hold
action: 0
With alarm hold
action: 2
R/W
Alarm 3 timer setting 0 to 6000 seconds (See P. 28)0R/W
Alarm 3
action selection at
input error
0: Normal processing
1: Forcibly turned on when abnormal
(See P. 29)
0R/W
Alarm 3
differential gap setting
0 (0.0) to span Note 1 R/W
Control output logic
selection 1
OUT1
0: Heat-side control output of CH1
3
OUT2
0: Heat-side control output of CH2
3
OUT3
0: Heat-side control output of CH3
3
OUT4
0: Heat-side control output of CH4
3
0
1
When using the FAIL alarm, always set the alarm type to “0: No alarm.”
2
The alarm hold action can not be added to the FAIL alarm, SV high alarm, SV low alarm, control
loop break alarm and heater break alarm.
3
This data is 0 fixation. This data must not set the set value besides 0.
Note 1 TC and RTD inputs: 2 °C [°F] or 2.0 °C [°F]
Voltage input: 0.2 % of span