Specifications

3. INITIALIZE COMMUNICATION DATA
IMR01H03-E4
37
Continued from the previous page.
Name Iden-
tifier
No. of
digits
Data range Factory set
value
Attri-
bute
CH
Alarm output
logic selection *
EA 6 0: FAIL alarm
1: Logical OR of alarm 1 in all
channels (Energized)
2: Logical OR of alarm 2 in all
channels (Energized)
3: Logical OR of alarm 3 in all
channels (Energized)
4: Logical OR of alarm 1 and
alarm 2 in all channels
(Energized)
5: Logical OR of alarm 1 and
alarm 3 in all channels
(Energized)
6: Logical OR of alarm 2 and
alarm 3 in all channels
(Energized)
7: Logical OR of alarm 1,
alarm 2 and alarm 3 in all
channels (Energized)
8: Logical OR of alarm 1 in all
channels (De-energized)
9: Logical OR of alarm 2 in all
channels (De-energized)
10: Logical OR of alarm 3 in all
channels (De-energized)
11: Logical OR of alarm 1 and
alarm 2 in all channels
(De-energized)
12: Logical OR of alarm 1 and
and 3 of all channels
(De-energized)
13: Logical OR of alarm 2 and
alarm 3 in all channels
(De-energized)
14: Logical OR of alarm 1,
alarm 2 and alarm 3 in all
channels (De-energized)
Alarm 1: 1
Alarm 2: 2
Alarm 3: 3
R/W
* The logic of alarm output can be set for each alarm (alarm 1 to alarm 3). When selecting the logic,
as a channel number specified after the identifier, specify any of the following numbers.
Alarm 1: 01 Alarm 2: 02 Alarm 3: 03
For the data structure, see the Communication Instruction Manual (IMR01H02-E
#
##
#
)
.
Continued on the next page.