Specifications
3. INITIALIZE COMMUNICATION DATA
IMR01H03-E4
34
Continued from the previous page.
Name Iden-
tifier
No. of
digits
Data range Factory set
value
Attri-
bute
CH
Contact input
logic selection *
XK
1 0 to 9
See contact input logic tables
0R/W
×
* This is the identifier effective when the contact input is provided.
Contact input logic tables
Set value STOP selection Memory area
selection
Used/Unused of
DI SET terminal (No.43)
0 When contact input (RUN/STOP
transfer) opens, stop.
Memory area
transfer 1 to 8
Used
1 When contact input (RUN/STOP
transfer) opens, stop.
Memory area
transfer 1 to 8
Unused
2 When contact input (RUN/STOP
transfer) opens, stop.
Memory area
transfer 1 to 7
Used
3 When contact input (RUN/STOP
transfer) opens, stop.
Memory area
transfer 1 to 7
Unused
4 When contact input (RUN/STOP
transfer) opens, stop.
There is no
memory area
transfer function.
Unused
5 When contact input (RUN/STOP
transfer) is closed, stop.
Memory area
transfer 1 to 8
Used
6 When contact input (RUN/STOP
transfer) is closed, stop.
Memory area
transfer 1 to 8
Unused
7 When contact input (RUN/STOP
transfer) is closed, stop.
Memory area
transfer 1 to 7
Used
8 When contact input (RUN/STOP
transfer) is closed, stop.
Memory area
transfer 1 to 7
Unused
9 When contact input (RUN/STOP
transfer) is closed, stop.
There is no
memory area
transfer function.
Unused
For details of the selection item, see the 2.5 F24 Contact Input Specification (P. 22).
Continued on the next page.